Currently Skimming:


Pages 104-110

The Chapter Skim interface presents what we've algorithmically identified as the most significant single chunk of text within every page in the chapter.
Select key terms on the right to highlight them within pages of the chapter.


From page 104...
... As a consequence, the Burnley Tunnel, which opened in late December 2000, is now widely regarded as an example of a modern safety model. Despite a potentially huge fire and the presence of more than 400 people in the tunnel, only three people died from the traffic accident and none from the subsequent fire.
From page 105...
... . One study came to the conclusion that, although some minimum water application rates would achieve a certain objective, a marginally higher rate would not necessarily improve the situation (79)
From page 106...
... Typically, the higher the FHRR, the more the water evaporates. • Does the water requirement depend on fire size at the time of fixed fire suppression system activation?
From page 107...
... . FIGURE 37 Accidental activation of the sprinkler fire suppression system in Boston CANA (Central Artery North Area Tunnel)
From page 108...
... Longitudinal ventilation -- unidirectional tunnel with manageable traffic Reduced fire size may result in reduced ventilation rate Increases mass of air/water mixture to move -- increases vent rate Cools environment and protects fan units from high temperature Overcomes water curtains created by the FFSS -- increases vent rate essaercni -- erifehtmorfyawasecnatsbusSFFehtswolBlarenegeeS number of FFS zones for activation. Longitudinal ventilation -- unidirectional tunnel with unmanageable traffic or bidirectional tunnel Protects tunnel structure Destroys stratification making evacuation difficult (maybe impossible)
From page 109...
... It is now recognized that the purpose of a waterbased fixed firefighting system is not to extinguish the fire but to prevent fire spread to other vehicles so that the fire does not grow to a size that cannot be attacked by the fire service.
From page 110...
... • With transverse ventilation, a short system activation delay may need to be considered. • Delay with the fixed fire suppression system activation will require additional water supply because of the larger fire size at the time of activation.